INSTRUCTION MANUAL FOR DIGITAL GENSET CONTROLLER DGC-2020 Publication: 9400200990 Revision: K 01/09

Pagina 2

viii DGC-2020 Introduction 9400200990 Rev K This page intentionally left blank.

Pagina 3

Figure 4-27. Programmable Functions Settings A Auto Transfer Switch Input: Select Input (None,

Pagina 4 - HIGHLAND IL 62249 USA

Figure 4-28. Remote LSM InputsSettings A Input Type: Voltage or Current. B Min/Max Input Voltag

Pagina 5 - REVISION HISTORY

Select the input typeB and amount of hysteresisC. A user-adjustable arming delayD disables analog input recognition during engine startup. When enable

Pagina 7

Remote Thermocouple Inputs An optional AEM-2020 (Analog Expansion Module) provides two thermocouple inputs. To make identifying the thermocouple input

Pagina 8

Figure 4-33. Contact Outputs Settings A Label Text: An alphanumeric character string with a ma

Pagina 9 - CONTENTS

BESTCOMSPlus settings for remote contact inputs (DGC-2020, Programmable Outputs, Remote Contact Outputs) are illustrated in Figure 4-35. Figure 4-35

Pagina 11 - TABLE OF CONTENTS

4-38 DGC-2020 BESTCOMSPlus Software 9400200990 Rev K

Pagina 12

9400200990 Rev K DGC-2020 BESTCOMSPlus Software 4-39 down to zero from the threshold time setting. The maintenance interval pre-alarm can be reset t

Pagina 13 - DESCRIPTION

9400200990 Rev K DGC-2020 General Information i SECTION 1  GENERAL INFORMATION TABLE OF CONTENTS SECTION 1  GENERAL INFORMATION ...

Pagina 14

4-40 DGC-2020 BESTCOMSPlus Software 9400200990 Rev K GOV Bias Output Limit GOV bias output limit settingsO consist of an enable/disable setting and

Pagina 15 - STYLE AND PART NUMBERS

Figure 4-38. Pre-Alarms Configuration A High Fuel Level: Enable or Disable, threshold is adjust

Pagina 16 - SPECIFICATIONS

4-42 DGC-2020 BESTCOMSPlus Software 9400200990 Rev K

Pagina 17

Note: ECU Support must be enabled on the Communications, CANbus Setup screen before this alarm can be configured. Figure 4-39. Alarms Configuration

Pagina 18

Figure 4-40. Sender Fail Configuration A Coolant Temp Sender Fail: None, Alarm, or Pre-Alarm, t

Pagina 19

The hysteresis settingD functions as an undervoltage dropout by preventing rapid switching of the pickup output. A frequency-based inhibit settingE pr

Pagina 20

settings. For example, if a scale factor contact input is received by the DGC-2020 and the scale factor setting is 2.000, the pickup setting will be d

Pagina 23

Figure 4-46. Generator Capability Curve vs. 40Q Response If reactive power is within the 40Q tripping region for the duration of the 40Q activation

Pagina 24

ii DGC-2020 General Information 9400200990 Rev K Underfrequency (81U) and Overfrequency (81O) ...

Pagina 25

4-50 DGC-2020 BESTCOMSPlus Software 9400200990 Rev K Overcurrent Protection (51-1, 51-2, 51-3) Two sets of overcurrent settings are provided for eac

Pagina 26

Figure 4-48. Overcurrent Protection Settings A Pickup: Adjustable from 0.9 to 7.75 Aac for 5 Aa

Pagina 27 - FRONT PANEL

During synchronization of the generator with the bus (Anticipatory mode only), the DGC-2020 uses the breaker closing timeJ to calculate the optimum ti

Pagina 29

Figure 4-50. Bus Condition Detection Settings A Dead Bus Threshold: Adjustable from 0 to 4,800

Pagina 30 - P0053-52

that is required to compensate for the breaker closure time by monitoring the frequency difference between the generator and the bus. BESTCOMSPlus aut

Pagina 31 - RUN STATISTICS

4-56 DGC-2020 BESTCOMSPlus Software 9400200990 Rev K

Pagina 32 - ALARMS-STATUS

droop is also the mode when the generator breaker is closed if kW load sharing is disabled. If it is desired to disable voltage droop, set the droop p

Pagina 33 - GENERAL SETTINGS

4-58 DGC-2020 BESTCOMSPlus Software 9400200990 Rev K

Pagina 34 - SYSTEM PARAMS

Expected rpm reduction in droop - (actual load/machine capacity)  (droop percentage/100)  rated speed. If the actual rpm drop does not match the exp

Pagina 35

9400200990 Rev K DGC-2020 General Information 1-1 SECTION 1  GENERAL INFORMATION DESCRIPTION The DGC-2020 Digital Genset Controller provides integr

Pagina 37 - PROGRAMMABLE INPUTS

Figure 4-55. Governor Output Settings A Output Type: Voltage or Current. B Response: Increasi

Pagina 38

Figure 4-57. Demand Start/Stop A Demand Start Stop Enable: Enable or Disable. B Delayed Start L

Pagina 39

Balanced Service Time If this mode is selected, units will seek to sort the start priority of all non-disabled networked units in ascending order of s

Pagina 40

BESTCOMSPlus network configuration settings (DGC-2020, Multigen Management, Network Configuration) are illustrated in Figure 4-59. Figure 4-59. Netw

Pagina 41

Figure 4-60. Programmable Senders Settings A Sender Points: Accepts up to 11 user-defined sende

Pagina 42 - BIAS CONTROL

Opening a Settings File To open a new instance of a settings file into BESTCOMSPlus, pull down the File menu and choose Open. The Open dialog box appe

Pagina 43

A dialog box will appear and notify you if any differences were found. The BESTCOMSPlus Settings Compare dialog box (Figure 4-62) is displayed where y

Pagina 44

CAUTION The order in which the components are upgraded is critical. Assuming a system of a DGC-2020 and expansion modules is in a state where the DGC-

Pagina 45

8. Click on the Upload button and the Proceed with Device Upload screen will appear. Select Yes or No. 9. After selecting Yes, the DGC-2020 Selection

Pagina 46

1-2 DGC-2020 General Information 9400200990 Rev K Contact Inputs and Output Contacts DGC-2020 controllers have one, dedicated emergency stop contact

Pagina 47

f. Click the Upload button and follow the instructions that appear to begin the upgrade process. g. After the upload is complete, disconnect communic

Pagina 48

9400200990 Rev K DGC-2020 BESTCOMSPlus Software 4-71 5. Load the new settings file into the DGC-2020. a. Disconnect communication from the DGC-202

Pagina 49 - DGC-2020 FUNCTION BLOCKS

4-72 DGC-2020 BESTCOMSPlus Software 9400200990 Rev K METERING EXPLORER The Metering Explorer is a convenient tool within BESTCOMSPlus used to naviga

Pagina 50

P0042-1509-20-06ACEBD Figure 4-66. Metering, Docking Options Table 4-2. Explanation of Call-Outs on Figure 4-66 Call-Out Symbol Explanation A Holdin

Pagina 51

Engine This screen provides information and metering of engine components. Refer to Figure 4-67. Figure 4-67. Metering, Engine Generator This screen

Pagina 52

Bias Control This screen provides Var/PF mode status and operating levels. Refer to Figure 4-70. Figure 4-70. Metering, Bias Control Run Statistics

Pagina 53

Figure 4-72. Metering, Status Inputs Contact Inputs This screen indicates the status of contact inputs, contact input alarms, and contact input pre-a

Pagina 54

Remote LSM Inputs When an optional LSM-2020 (Load Share Module) is connected, the value of the analog inputs is displayed on this screen. Voltage is d

Pagina 55

Remote RTD Inputs When an optional AEM-2020 (Analog Expansion Module) is connected, the status of the remote RTD inputs, remote RTD input alarms, and

Pagina 56

Figure 4-79. Metering, Inputs, Remote Analog Input Values The Calibrate button shown in Figure 4-79 opens the Analog Input Temperature Calibration s

Pagina 57 - MODES OF OPERATION

AEM-2020 (ANALOG EXPANSION MODULE) The optional AEM-2020 provides eight remote analog inputs, eight remote RTD inputs, two remote thermocouple inputs,

Pagina 58

Outputs Contact Outputs This screen indicates the status of contact outputs. The status is TRUE when the corresponding LED is green. Refer to Figure 4

Pagina 59

Figure 4-83. Metering, Outputs, Remote Contact Outputs Remote Analog Outputs When an optional AEM-2020 (Analog Expansion Module) is connected, the s

Pagina 60 - EVENT RECORDING

Figure 4-85. Metering, Alarms Event Log The event log provides a historical record of event occurrences detected by the DGC-2020. It is saved in nonv

Pagina 61 - Table 3-4. Event List

Figure 4-86. Metering, Event Log, Sorted by Date When viewed with BESTCOMSPlus, the event log can be sorted by Event ID, Description, Occurrence, Da

Pagina 62

Figure 4-88. Metering, ECU Data Engine Configuration This screen displays Engine Configuration. Refer to Figure 4-89. Figure 4-89. Metering, Engin

Pagina 63

Figure 4-90. Metering, Download DTC MTU The MTU reports operating information to the DGC-2020 through the CANbus interface when the ECU is configured

Pagina 64

MTU Status MTU Status is reported on this screen. The status is TRUE when the corresponding LED is red. Refer to Figure 4-93. Figure 4-93. Metering,

Pagina 65

Summary This screen displays a metering summary. Refer to Figure 4-95. Figure 4-95. Metering, Summary 9400200990 Rev K DGC

Pagina 66

Control Controls for stopping/starting the engine, controls for opening/closing breakers, and controls for opening/closing switches are accessed thro

Pagina 67

Generator Network Status This screen (Figure 4-98) displays the detected sequencing IDs of the LSM-2020’s on the network. This can only be accomplishe

Pagina 68

1-4 DGC-2020 General Information 9400200990 Rev K Part Numbers A ten-digit part number specifies the electrical characteristics and operational feat

Pagina 69

4-90 DGC-2020 BESTCOMSPlus Software 9400200990 Rev K This page intentionally left blank.

Pagina 70

9400200990 Rev K DGC-2020 BESTlogic+ Programmable Logic i SECTION 5  BESTlogic+ PROGRAMMABLE LOGIC TABLE OF CONTENTS SECTION 5  BESTlogic+ PROGRA

Pagina 71

ii DGC-2020 BESTlogic+ Programmable Logic 9400200990 Rev K This page intentionally left blank.

Pagina 72 - STARTUP AND ACTIVATION

SECTION 5  BESTlogic+ PROGRAMMABLE LOGIC INTRODUCTION BESTlogic+ Programmable Logic is a programming method used for managing the input, output, prot

Pagina 73

BESTlogic+ Composition There are three main groups of objects used for programming BESTlogic+. These groups are I/O, Components, and Elements. For det

Pagina 74 - COMMUNICATION

Name Description Symbol Status Input Auto Restart TRUE when the Automatic Restart function is active. Status Input Battery Charger Fail TRUE when th

Pagina 75

Name Description Symbol Status Input Front Panel Buttons TRUE while the EDIT front panel button is pressed. Status Input Front Panel Buttons TRUE wh

Pagina 76

Name Description Symbol Status Input Load Share Module Load Share Module Connected. TRUE when an optional LSM-2020 is connected to the DGC-2020. Sta

Pagina 77

Name Description Symbol Alarms Analog Expansion Module Remote Analog Inputs 1-8 TRUE when Over 1, Over 2, Under 1, Under 2, or Out of Range is config

Pagina 78 - MENU BARS

Name Description Symbol Hi Coolant Temp TRUE when the High Coolant Temp Alarm settings have been exceeded. Low Coolant Level TRUE when the Low Coo

Pagina 79 - SETTINGS EXPLORER

9400200990 Rev K DGC-2020 General Information 1-5 Contact Sensing Contact sensing inputs include 1 emergency stop input and 16 programmable inputs.

Pagina 80

Name Description Symbol Battery Charger Fail TRUE when the Battery Charger Fail function is configured as a Pre-Alarm and the activation delay has e

Pagina 81

Name Description Symbol Hi Coolant Temp TRUE when the High Coolant Temp Pre-Alarm threshold has been exceeded. High Fuel Level TRUE when the High

Pagina 82

Name Description Symbol Senders Coolant Temp Sender Fail TRUE when the Coolant Temp Sender Fail is configured as either a Pre-Alarm or Alarm and the

Pagina 83

Name Description Symbol XOR Input Output 0 0 0 0 1 1 1 0 1 1 1 0 XNOR Input Output 0 0 1 0 1 0 1 0 0 1 1 1 NOT (INVERTER) Input Output 0

Pagina 84

Table 5-3. Elements Group, Names and Descriptions Name Description Symbol Protection 27-1TRIP TRUE when the 27-1 undervoltage is in a TRIP condition

Pagina 85

Name Description Symbol Other ATS When this logic element is TRUE, and the DGC-2020 is in AUTO mode, the generator will run. This can be used in pla

Pagina 86

Name Description Symbol COOLDOWNREQ RUN Mode If the unit is in RUN mode when the Cool Down Request is received, the unit is forced to unload and open

Pagina 87

Name Description Symbol GENBRK This element is used to connect the breaker open and close output signals from the DGC-2020 to physical output contac

Pagina 88

Name Description Symbol MAINSBRK This element is used to connect the breaker open and close output signals from the DGC-2020 to physical output cont

Pagina 89

Name Description Symbol PARTOMAINS Setting this logic element to TRUE indicates to the DGC-2020 that it is paralleled to a utility. When parallele

Pagina 90

1-6 DGC-2020 General Information 9400200990 Rev K Programmable Relays (12) Rating: 2 Adc at 30 Vdc—make, break, and carry Terminals† Output 1: 5

Pagina 91 - SYSTEM PARAMETERS

Name Description Symbol STARTOUTPUT This element is used to drive the start output relay from logic when the Start Output Relay configuration is set

Pagina 92

CAUTION Modifying a logic scheme in BESTCOMSPlus does not automatically make that scheme active in the DGC-2020. The modified scheme must be uploaded

Pagina 93

Pickup and Dropout Timers A pickup timer produces a TRUE output when the elapsed time is greater than or equal to the Pickup Time setting after a FALS

Pagina 94

Opening a BESTlogic+ File To open a saved BESTlogic+ file, click on the Logic Library drop-down button on the BESTlogic+ Programmable Logic toolbar an

Pagina 95

Example 2 - AND Gate Connections Figure 5-5 illustrates a typical AND gate connection. In this example, Output 11 will become active when the Low Fuel

Pagina 96

9400200990 Rev K DGC-2020 Installation i SECTION 6  INSTALLATION TABLE OF CONTENTS SECTION 6  INSTALLATION ...

Pagina 97

ii DGC-2020 Installation 9400200990 Rev K Figure 6-16. Single-Phase A-B Connections for MTU MDEC ECU Applications...

Pagina 98

SECTION 6  INSTALLATION GENERAL DGC-2020 controllers are delivered in sturdy cartons to prevent shipping damage. Upon receipt of a system, check the

Pagina 99

Figure 6-2. Overall Dimensions 6-2 DGC-2020 Installation 9400200990 Rev K

Pagina 100

CONNECTIONS DGC-2020 connections are dependent on the application. Incorrect wiring may result in damage to the controller. NOTE Be sure that the DGC-

Pagina 101

9400200990 Rev K DGC-2020 General Information 1-7 Apparent Power Indicates total kVA and individual line kVA (4-wire, line-to-neutral or 3-wire, lin

Pagina 102

Table 6-2. Generator Current Sensing Terminals Terminal Description 68 (IA–) 69 (IA+) A-phase current sensing input 71 (IB–) 72 (IB+) B-phase current

Pagina 103

Table 6-5. Sender Input Terminals Terminal Description 8 (OIL) Oil pressure sender input 9 (FUEL) Fuel level sender input 10 (COOLANT) Coolant temp

Pagina 104 - PROGRAMMABLE OUTPUTS

6-6 DGC-2020 Installation 9400200990 Rev K Magnetic Pickup Input The magnetic pickup input accepts a speed signal over the range of 3 to 35 volts pe

Pagina 105

9400200990 Rev K DGC-2020 Installation 6-7 Table 6-9. Programmable Output Contact Terminals Terminal Description 51 (COM 1, 2, 3) Common connection

Pagina 106

NOTES 1.) If the DGC-2020 is providing one end of the J1939 bus, a 120  terminating resistor should be installed across terminals 48 (CANL) and 49 (

Pagina 107 - CONFIGURABLE PROTECTION

9400200990 Rev K DGC-2020 Installation 6-9 Dial-Out Modem DGC-2020 controllers with style number xxxxxMxxx have an internal modem with dial-in, dial

Pagina 108 - ALARM CONFIGURATION

3-Phase Wye Connections for Typical Applications Figure 6-6. 3-Phase Wye Connections for Typical Applications 6-10 DGC-2020 Installation 9400200990

Pagina 109

3-Phase Delta Connections for Typical Applications Figure 6-7. 3-Phase Delta Connections for Typical Applications 9400200990 Rev K DGC-2020 Installa

Pagina 110

Single-Phase A-B Connections for Typical Applications Figure 6-8. Single-Phase A-B Connections for Typical Applications 6-12 DGC-2020 Installation

Pagina 111

Single-Phase A-C Connections for Typical Applications Figure 6-9. Single-Phase A-C Connections for Typical Applications 9400200990 Rev K DGC-2020 In

Pagina 113

1-8 DGC-2020 General Information 9400200990 Rev K Maintenance Timer Maintenance timer indicates the time remaining until genset service is due. Valu

Pagina 114 - GENERATOR PROTECTION

6-14 DGC-2020 Installation 9400200990 Rev K Connections for Volvo Penta EDC III Applications Engines equipped with Volvo Penta EDC III controllers c

Pagina 115

3-Phase Wye Connections for Volvo Penta EDC III Applications Figure 6-10. 3-Phase Wye Connections for Volvo Penta EDC III Applications 9400200990 Rev

Pagina 116

3-Phase Delta Connections for Volvo Penta EDC III Applications Figure 6-11. 3-Phase Delta Connections for Volvo Penta EDC III Applications 6-16 DGC-

Pagina 117

Single-Phase A-B Connections for Volvo Penta EDC III Applications Figure 6-12. Single-Phase A-B Connections for Volvo Penta EDC III Applications 9400

Pagina 118

Single-Phase A-C Connections for Volvo Penta EDC III Applications Figure 6-13. Single-Phase A-C Connections for Volvo Penta EDC III Applications 6-18

Pagina 119

9400200990 Rev K DGC-2020 Installation 6-19 Connections for MTU MDEC ECU Applications MTU MDEC ECUs, supplied on some Detroit Diesel engines, can re

Pagina 120

3-Phase Wye Connections for MTU MDEC ECU Applications Figure 6-14. 3-Phase Wye Connections for MTU MDEC ECU Applications 6-20 DGC-2020 Installatio

Pagina 121 - BREAKER MANAGEMENT

3-Phase Delta Connections for MTU MDEC ECU Applications Figure 6-15. 3-Phase Delta Connections for MTU MDEC ECU Applications 9400200990 Rev K DGC-

Pagina 122

Single-Phase A-B Connections for MTU MDEC ECU Applications Figure 6-16. Single-Phase A-B Connections for MTU MDEC ECU Applications 6-22 DGC-2020 I

Pagina 123

Single-Phase A-C Connections for MTU MDEC ECU Applications Figure 6-17. Single-Phase A-C Connections for MTU MDEC ECU Applications 9400200990 Rev

Pagina 124

Logic Timers Range: 0 to 10 s Increment: 0.1 s Accuracy: 15 ms Communication Interface USB Specification Compatibility: USB 2.0 Data Transfer Spe

Pagina 125

Connections with AEM-2020, CEM-2020, and LSM-2020 The AEM-2020 (Analog Expansion Module), CEM-2020 (Contact Expansion Module), and LSM-2020 (Load Shar

Pagina 126 - BIAS CONTROL SETTINGS

9400200990 Rev K DGC-2020 Maintenance and Troubleshooting i SECTION 7  MAINTENANCE AND TROUBLESHOOTING TABLE OF CONTENTS SECTION 7  MAINTENANCE A

Pagina 127

ii DGC-2020 Maintenance and Troubleshooting 9400200990 Rev K This page intentionally left blank.

Pagina 128

SECTION 7  MAINTENANCE AND TROUBLESHOOTING MAINTENANCE Preventative maintenance consists of periodic replacement of the backup battery (optional) and

Pagina 129

7-2 DGC-2020 Maintenance and Troubleshooting 9400200990 Rev K Step 3. Verify that all Ethernet devices comply with IEC 61000-4 series of specifica

Pagina 130 - MULTIGEN MANAGEMENT

9400200990 Rev K DGC-2020 Maintenance and Troubleshooting 7-3 Step 2. Ensure that the proper current is present at the DGC-2020 current sensing in

Pagina 131

7-4 DGC-2020 Maintenance and Troubleshooting 9400200990 Rev K the logic output that would normally be the breaker close output. Map another virtual

Pagina 132

9400200990 Rev K DGC-2020 Maintenance and Troubleshooting 7-5 Synchronizer Determining if the Synchronizer is Active Step 1: Disable the speed tr

Pagina 133

7-6 DGC-2020 Maintenance and Troubleshooting 9400200990 Rev K If the speed still does not change when varying the bias:  Verify that the gov

Pagina 134 - PROGRAMMABLE SENDERS

9400200990 Rev K DGC-2020 LSM-2020 (Load Share Module) i SECTION 8  LSM-2020 (LOAD SHARE MODULE) TABLE OF CONTENTS TTSECTION 8  LSM-2020 (LOAD SH

Pagina 135 - FILE MANAGEMENT

CAUTION Replacement of the backup battery for the real-time clock should be performed only by qualified personnel. Do not short-circuit the battery, r

Pagina 136

ii DGC-2020 LSM-2020 (Load Share Module) 9400200990 Rev K Figures UUFigure 8-1. Device Info Screen...

Pagina 137

9400200990 Rev K DGC-2020 LSM-2020 (Load Share Module) 8-1 SECTION 8  LSM-2020 (LOAD SHARE MODULE) GENERAL INFORMATION The LSM-2020 is a remote aux

Pagina 138

8-2 DGC-2020 LSM-2020 (Load Share Module) 9400200990 Rev K Communication Interface CANbus Differential Bus Voltage: 1.5 to 3 Vdc Maximum Voltage:

Pagina 139

9400200990 Rev K DGC-2020 LSM-2020 (Load Share Module) 8-3 CE Compliance This product complies with the requirements of the following EC Directives:

Pagina 140

8-4 DGC-2020 LSM-2020 (Load Share Module) 9400200990 Rev K Generator Sequencing Machines can be added or removed from the power system based on load

Pagina 141

Figure 8-1. Device Info Screen A Application Version: When configuring Load Share Module settin

Pagina 142 - METERING EXPLORER

Figure 8-2. Device Security Setup Screen A Access Level/Password: Read-only value obtained when

Pagina 143 - 09-20-06

5.50 [139.7]151617186.38 [162.0]7.50 [190.5] 8.38 [212.8]1.39 [35.3]1234567891011121314P0052-36P2J3 Figure 8-3. LSM-2020 Overall Dimensions Connection

Pagina 144

8-8 DGC-2020 LSM-2020 (Load Share Module) 9400200990 Rev K Operating Power The LSM-2020 operating power input accepts either 12 Vdc or 24 Vdc and to

Pagina 145

CANbus Interface These terminals provide communication using the SAE J1939 protocol and provide high-speed communication between the LSM-2020 and the

Pagina 146

UL/CSA Approval “cURus” recognized to UL Standard 508 & CSA Standard C22.2 No. 14. CSA certified to CSA C22.2 No. 14. Part Numbers 9400200105 and

Pagina 147

AEM-2020(Optional)DGC-2020Other DevicesP0053-59Engine120 ohmTerminationCAN-HCAN-LCEM-2020 (Optional)LSM-2020120 ohmTerminationBusStub Figure 8-5. CANb

Pagina 148

DGC-2020GEN ENGINEGOVLSM-2020AVR17181415101112CANLCANHGNDAVR+AVR-GOV+GOV-504948 CANLCANHGND56LS+LS-DGC-2020GEN ENGINEGOVLSM-2020AVR17181415101112CANLC

Pagina 149

Connections using AVR’, GOV’, and LS’ Additional terminals provide a landing point to add series resistance to the GOV, AVR, and LS analog outputs. Th

Pagina 150

123456789101112131415161718EthernetLSM-2020AVR+AVR-AVR’GOV+GOV-GOV’CANLCANHGNDV+IN-I+LS+LS-LS’B-B+GNDGovernorAnalog Aux InputDGC-2020CANLCANHSHIELDP00

Pagina 151

8-14 DGC-2020 LSM-2020 (Load Share Module) 9400200990 Rev K This page intentionally left blank.

Pagina 152

9400200990 Rev K DGC-2020 CEM-2020 (Contact Expansion Module) i SECTION 9  CEM-2020 (CONTACT EXPANSION MODULE) TABLE OF CONTENTS SECTION 9  CEM-2

Pagina 153

ii DGC-2020 CEM-2020 (Contact Expansion Module) 9400200990 Rev K This page intentionally left blank.

Pagina 154

9400200990 Rev K DGC-2020 CEM-2020 (Contact Expansion Module) 9-1 SECTION 9  CEM-2020 (CONTACT EXPANSION MODULE) GENERAL INFORMATION The optional C

Pagina 155

9-2 DGC-2020 CEM-2020 (Contact Expansion Module) 9400200990 Rev K HALT (Highly Accelerated Life Testing) HALT is used by Basler Electric to prove th

Pagina 156

BESTCOMSPlus SOFTWARE BESTCOMSPlus provides the user with a point-and-click means to set and monitor the Contact Expansion Module. Installation and op

Pagina 157

1-12 DGC-2020 General Information 9400200990 Rev K This page intentionally left blank.

Pagina 158

Connections Contact Expansion Module connections are dependent on the application. Incorrect wiring may result in damage to the module. NOTE Operating

Pagina 159 - CONVERTING SETTINGS FILES

Figure 9-2. CEM-2020 Input Contact and Output Contact Terminals CANbus Interface These terminals provide communication using the SAE J1939 protocol

Pagina 160

NOTES 1.) If the CEM-2020 is providing one end of the J1939 bus, a 120  terminating resistor should be installed across terminals P1- LO (CANL) and

Pagina 161

9400200990 Rev K DGC-2020 AEM-2020 (Analog Expansion Module) i SECTION 10  AEM-2020 (ANALOG EXPANSION MODULE) TABLE OF CONTENTS SECTION 10  AEM-2

Pagina 162

ii DGC-2020 AEM-2020 (Analog Expansion Module) 9400200990 Rev K This page intentionally left blank.

Pagina 163 - OVERVIEW OF BESTlogic+

9400200990 Rev K DGC-2020 AEM-2020 (Analog Expansion Module) 10-1 SECTION 10  AEM-2020 (ANALOG EXPANSION MODULE) GENERAL INFORMATION The optional A

Pagina 164

10-2 DGC-2020 AEM-2020 (Analog Expansion Module) 9400200990 Rev K Type Tests Shock 15 G in 3 perpendicular planes Vibration Swept over the following

Pagina 165

9400200990 Rev K DGC-2020 AEM-2020 (Analog Expansion Module) 10-3 FUNCTIONAL DESCRIPTION A functional description of the AEM-2020’s inputs and outpu

Pagina 166

Mounting Analog Expansion Modules are contained in an encapsulated plastic case and may be mounted in any convenient position. The construction of a A

Pagina 167

is mounted permanently to the board. Connector screw terminals accept a maximum wire size of 12 AWG. Thermocouple connectors accept a maximum thermoco

Pagina 168

9400200990 Rev K DGC-2020 Human-Machine Interface i SECTION 2  HUMAN-MACHINE INTERFACE TABLE OF CONTENTS SECTION 2  HUMAN-MACHINE INTERFACE ...

Pagina 169

Table 10-2. Input and Output Terminals Connector Description P1 Operating Power and CANbus P2 RTD Inputs 1 - 8 P3 Analog Inputs 1 - 8 and Analog Ou

Pagina 170

Table 10-3. CANbus Interface Terminals Terminal Description P1- HI (CAN H) CAN high connection (yellow wire) P1- LO (CAN L) CAN low connection (gree

Pagina 171

AEM-2020DGC-2020Other DevicesP0053-63Engine120 ohmTerminationCAN-HCAN-LLSM-2020(Optional)CEM-2020(Optional)120 ohmTerminationBusStub Figure 10-6. CANb

Pagina 172

9400200990 Rev K DGC-2020 Time Overcurrent Characteristic Curves i APPENDIX A  TIME OVERCURRENT CHARACTERISTIC CURVES TABLE OF CONTENTS APPENDIX A

Pagina 173

ii DGC-2020 Time Overcurrent Characteristic Curves 9400200990 Rev K This page intentionally left blank.

Pagina 174

APPENDIX A  TIME OVERCURRENT CHARACTERISTIC CURVES INTRODUCTION The inverse time overcurrent characteristic curves provided by the DGC-2020 (style xx

Pagina 175

A-2 DGC-2020 Time Overcurrent Characteristic Curves 9400200990 Rev K Table A-1. 51 Time Characteristic Curve Constants Trip Characteristic Constants

Pagina 176

9400200990 Rev K DGC-2020 Time Overcurrent Characteristic Curves A-3 Table A-2. Characteristic Curve Cross-Reference Curve Curve Name Similar To S1

Pagina 177

A-4 DGC-2020 Time Overcurrent Characteristic Curves 9400200990 Rev K Table A-3 .Time Dial Setting Cross-Reference Electromechanical R

Pagina 178

Figure A-1. Time Characteristic Curve S, S1, Short Inverse (Similar to ABB CO-2) 9400200990 Rev K DGC-2020 Time Overcurrent Characteristic Curves A

Pagina 179

ii DGC-2020 Human-Machine Interface 9400200990 Rev K This page intentionally left blank.

Pagina 180 - LOGIC SCHEMES

A-6 DGC-2020 Time Overcurrent Characteristic Curves 9400200990 Rev K Figure A-2. Time Characteristic Curve S2, Short Inverse (Similar To GE IAC-55)

Pagina 181 - PROGRAMMING BESTlogic+

9400200990 Rev K DGC-2020 Time Overcurrent Characteristic Curves A-7 Figure A-3. Time Characteristic Curve L, L1, Long Inverse (Similar to ABB CO-5

Pagina 182 - P0048-03

Figure A-4. Time Characteristic Curve L2, Long Inverse (Similar To GE IAC-66) A-8 DGC-2020 Time Overcurrent Characteristic Curves 9400200990 Rev

Pagina 183 - BESTlogic+ EXAMPLES

Figure A-5. Time Characteristic Curve D, Definite Time (Similar To ABB CO-6) 9400200990 Rev K DGC-2020 Time Overcurrent Characteristic Curves A-9

Pagina 184

Figure A-6. Time Characteristic Curve M, Moderately Inverse (Similar to ABB CO-7) A-10 DGC-2020 Time Overcurrent Characteristic Curves 9400200990

Pagina 185 - SECTION 6  INSTALLATION

Figure A-7. Time Characteristic Curve I, I1, Inverse Time (Similar to ABB CO-8) 9400200990 Rev K DGC-2020 Time Overcurrent Characteristic Curves

Pagina 186

Figure A-8. Time Characteristic Curve I2, Inverse Time (Similar to GE IAC-51) A-12 DGC-2020 Time Overcurrent Characteristic Curves 9400200990 Rev

Pagina 187

Figure A-9. Time Characteristic Curve V, V1, Very Inverse (Similar to ABB CO-9) 9400200990 Rev K DGC-2020 Time Overcurrent Characteristic Curves

Pagina 188

Figure A-10. Time Characteristic Curve V2, Very Inverse (Similar to GE IAC-53) A-14 DGC-2020 Time Overcurrent Characteristic Curves 9400200990 Re

Pagina 189 - CONNECTIONS

Figure A-11. Time Characteristic Curve E, E1, Extremely Inverse (Similar to ABB CO-11) 9400200990 Rev K DGC-2020 Time Overcurrent Characteristic C

Pagina 190

SECTION 2  HUMAN-MACHINE INTERFACE INTRODUCTION This section describes the components of the DGC-2020 human-machine interface (HMI). DGC-2020 HMI com

Pagina 191 - P0053-93

Figure A-12. Time Characteristic Curve E2, Extremely Inverse (Similar to GE IAC-77) A-16 DGC-2020 Time Overcurrent Characteristic Curves 94002009

Pagina 192

Figure A-13. Time Characteristic Curve A, Standard Inverse 9400200990 Rev K DGC-2020 Time Overcurrent Characteristic Curves A-17

Pagina 193

Figure A-14. Time Characteristic Curve B, Very Inverse A-18 DGC-2020 Time Overcurrent Characteristic Curves 9400200990 Rev K

Pagina 194 - P0053-95

Figure A-15. Time Characteristic Curve C, Extremely Inverse 9400200990 Rev K DGC-2020 Time Overcurrent Characteristic Curves A-19

Pagina 195

Figure A-16. Time Characteristic Curve G, Long Time Inverse A-20 DGC-2020 Time Overcurrent Characteristic Curves 9400200990 Rev K

Pagina 196

9400200990 Rev K DGC-2020 Modbus Communication i APPENDIX B  MODBUS COMMUNICATION TABLE OF CONTENTS APPENDIX B  Modbus COMMUNICATION ...

Pagina 197

ii DGC-2020 Modbus Communication 9400200990 Rev K This page intentionally left blank.

Pagina 198

9400200990 Rev K DGC-2020 Modbus Communication B-1 APPENDIX B  MODBUS COMMUNICATION INTRODUCTION General Overview An optional feature of the DGC-

Pagina 199

B-2 DGC-2020 Modbus Communication 9400200990 Rev K Data Block Field The query Data block contains additional information needed by the slave to perf

Pagina 200

9400200990 Rev K DGC-2020 Modbus Communication B-3  Function 08, Subfunction 00 - Diagnostics: Return Query Data  Function 16 - Preset Multiple

Pagina 201

2-2 DGC-2020 Human-Machine Interface 9400200990 Rev K Table 2-1. Front Panel HMI Descriptions Locator Description A Liquid Crystal Display. The bac

Pagina 202

B-4 DGC-2020 Modbus Communication 9400200990 Rev K Preset Multiple Registers, Non-Broadcast & Broadcast Preset Multiple Registers - General QUER

Pagina 203

9400200990 Rev K DGC-2020 Modbus Communication B-5  There are several instances of registers that are grouped together (signified as DP or TP) to

Pagina 204

B-6 DGC-2020 Modbus Communication 9400200990 Rev K Long Integer Data Format (INT32) The Modbus long integer data format uses two consecutive holding

Pagina 205

9400200990 Rev K DGC-2020 Modbus Communication B-7 The second register contains the low-order 16 bits of double precision data, and is the actual d

Pagina 206

B-8 DGC-2020 Modbus Communication 9400200990 Rev K MAPPING - DGC-2020 PARAMETERS INTO MODICON ADDRESS SPACE Table Conventions Table B-3 uses the con

Pagina 207

9400200990 Rev K DGC-2020 Modbus Communication B-9 Table B-3. Legacy Parameter Table Holding Register Parameter Range Read/Write Supported Data For

Pagina 208

B-10 DGC-2020 Modbus Communication 9400200990 Rev K Holding Register Parameter Range Read/Write Supported Data Format Units 40049 Threshold 3-100

Pagina 209

9400200990 Rev K DGC-2020 Modbus Communication B-11 Holding Register Parameter Range Read/Write Supported Data Format Units 40082 Alarm Codes indiv

Pagina 210 - CEM-2020

B-12 DGC-2020 Modbus Communication 9400200990 Rev K Holding Register Parameter Range Read/Write Supported Data Format Units 40110 Phase a RMS Curre

Pagina 211 - TROUBLESHOOTING

9400200990 Rev K DGC-2020 Modbus Communication B-13 Holding Register Parameter Range Read/Write Supported Data Format Units 40287-97 RESERVED

Pagina 212

9400200990 Rev K DGC-2020 Human-Machine Interface 2-3 Permissions If communications access is active through the modem or USB, the front panel will

Pagina 213

B-14 DGC-2020 Modbus Communication 9400200990 Rev K Holding Register Parameter Range Read/Write Supported Data Format Units 40322 Active DTC Number

Pagina 214

9400200990 Rev K DGC-2020 Modbus Communication B-15 Holding Register Parameter Range Read/Write Supported Data Format Units 40354 Previous DTC Numb

Pagina 215

B-16 DGC-2020 Modbus Communication 9400200990 Rev K Holding Register Parameter Range Read/Write Supported Data Format Units 40372 CAN Communications

Pagina 216

9400200990 Rev K DGC-2020 Modbus Communication B-17 Holding Register Parameter Range Read/Write Supported Data Format Units 40388 CANbus ECU Confi

Pagina 217

B-18 DGC-2020 Modbus Communication 9400200990 Rev K Holding Register Parameter Range Read/Write Supported Data Format Units 40444 Coolant Level 0

Pagina 218

9400200990 Rev K DGC-2020 Modbus Communication B-19 Holding Register Parameter Range Read/Write Supported Data Format Units 40468 Override Speed Po

Pagina 219

B-20 DGC-2020 Modbus Communication 9400200990 Rev K Holding Register Parameter Range Read/Write Supported Data Format Units 40509-604 RESERVED

Pagina 220

9400200990 Rev K DGC-2020 Modbus Communication B-21 Holding Register Parameter Range Read/Write Supported Data Format Units 40640 Gen Protection Pr

Pagina 221 - GENERAL INFORMATION

B-22 DGC-2020 Modbus Communication 9400200990 Rev K Holding Register Parameter Range Read/Write Supported Data Format Units 40761 MTU Pre-alarms 0-

Pagina 222

9400200990 Rev K DGC-2020 Modbus Communication B-23 Register Description Type Units Scaling Factor R/W Range 42052 Mains Breaker Status Int32 N/

Pagina 223 - FUNCTIONAL DESCRIPTION

INTRODUCTION This instruction manual provides information about the operation and installation of the DGC-2020 Digital Genset Controller. To accomplis

Pagina 224 - BESTCOMSPlus SOFTWARE

Changing a Setting To change a setting, navigate to the setting you want to change and press the Edit key. If you are not already logged in, you will

Pagina 225

B-24 DGC-2020 Modbus Communication 9400200990 Rev K Register Description Type Units Scaling Factor R/W Range 42328 kw Integrator Limit Plus Float

Pagina 226 - INSTALLATION

9400200990 Rev K DGC-2020 Modbus Communication B-25 Register Description Type Units Scaling Factor R/W Range 42768 Gen Sensing Stable Overfrequenc

Pagina 227 - P0052-36

B-26 DGC-2020 Modbus Communication 9400200990 Rev K Register Description Type Units Scaling Factor R/W Range 43502 Pre-Start Contact Config Int32

Pagina 228

9400200990 Rev K DGC-2020 Modbus Communication B-27 Register Description Type Units Scaling Factor R/W Range 43574 Speed Signal Source Uint32 N/

Pagina 229 - P0053-58

B-28 DGC-2020 Modbus Communication 9400200990 Rev K Register Description Type Units Scaling Factor R/W Range 43616 DST End Week of Month Int32 N/

Pagina 230 - Governor

9400200990 Rev K DGC-2020 Modbus Communication B-29 Register Description Type Units Scaling Factor R/W Range 43776 Virtual Input 1 Open Int32 N/

Pagina 231 - Ethernet

B-30 DGC-2020 Modbus Communication 9400200990 Rev K Register Description Type Units Scaling Factor R/W Range 44262 1 Phase Overcurrent Curve (51-1)

Pagina 232

9400200990 Rev K DGC-2020 Modbus Communication B-31 Register Description Type Units Scaling Factor R/W Range 44306 Underfrequency Alarm Configurat

Pagina 233 - External

B-32 DGC-2020 Modbus Communication 9400200990 Rev K Register Description Type Units Scaling Factor R/W Range 44338 3 Phase Undervoltage Activation

Pagina 234

9400200990 Rev K DGC-2020 Modbus Communication B-33 Register Description Type Units Scaling Factor R/W Range 44396 3 Phase Reverse Power Alarm Con

Pagina 235 - MODULE)

9400200990 Rev K DGC-2020 Human-Machine Interface 2-5  BUS V  BUS FREQ  SYNCHRONIZER POWER  kW A  kW B  kW C  kW TOTAL  kVA A  kVA

Pagina 236

B-34 DGC-2020 Modbus Communication 9400200990 Rev K Register Description Type Units Scaling Factor R/W Range 44516 Overspeed Alarm Enable Uint32

Pagina 237

9400200990 Rev K DGC-2020 Modbus Communication B-35 Register Description Type Units Scaling Factor R/W Range 44578 Maintenance Interval Pre-Alarm

Pagina 238

B-36 DGC-2020 Modbus Communication 9400200990 Rev K Register Description Type Units Scaling Factor R/W Range 44634 GOV Bias Output Limit Pre-alarm

Pagina 239 - P0056-98

9400200990 Rev K DGC-2020 Modbus Communication B-37 Register Description Type Units Scaling Factor R/W Range 44812 Alarm Metering Int32 N/A N/A

Pagina 240

B-38 DGC-2020 Modbus Communication 9400200990 Rev K Register Description Type Units Scaling Factor R/W Range 44828 Local Input Metering Int32 N/A

Pagina 241

9400200990 Rev K DGC-2020 Modbus Communication B-39 Register Description Type Units Scaling Factor R/W Range 44858 Session Total Engine Run Hrs. I

Pagina 242 - P0053-61

B-40 DGC-2020 Modbus Communication 9400200990 Rev K Register Description Type Units Scaling Factor R/W Range 44956 Local Configurable Inputs Alarm

Pagina 243

9400200990 Rev K DGC-2020 Modbus Communication B-41 Register Description Type Units Scaling Factor R/W Range 44966 Remote Outputs Status Bits Int3

Pagina 244

B-42 DGC-2020 Modbus Communication 9400200990 Rev K Register Description Type Units Scaling Factor R/W Range 45504 Analog Input 3 Metering Value In

Pagina 245

9400200990 Rev K DGC-2020 Modbus Communication B-43 Register Description Type Units Scaling Factor R/W Range 45538 AEM Input Threshold Status Bits

Pagina 246

2-6 DGC-2020 Human-Machine Interface 9400200990 Rev K ALARMS-STATUS  ALARMS  PRE-ALARMS  MTU FAULT CODES (Visible when ECU is configured for M

Pagina 247

B-44 DGC-2020 Modbus Communication 9400200990 Rev K Register Description Type Units Scaling Factor R/W Range 45544 AEM Input Threshold Alarm Bits R

Pagina 248 - P0056-97

9400200990 Rev K DGC-2020 Modbus Communication B-45 Register Description Type Units Scaling Factor R/W Range 45548 AEM Input Threshold Alarm Bits

Pagina 249

B-46 DGC-2020 Modbus Communication 9400200990 Rev K Register Description Type Units Scaling Factor R/W Range 45554 AEM Input Threshold Pre-Alarm Bi

Pagina 250 - P0053-65

9400200990 Rev K DGC-2020 Modbus Communication B-47 Register Description Type Units Scaling Factor R/W Range 45562 Analog Output 2 Metering Value

Pagina 251 - P0053-62

B-48 DGC-2020 Modbus Communication 9400200990 Rev K Register Description Type Units Scaling Factor R/W Range 45570 Configurable Protection Alarm Bit

Pagina 252 - MAINTENANCE

9400200990 Rev K DGC-2020 Modbus Communication B-49 Register Description Type Units Scaling Factor R/W Range 45576 Gen Kvar B Int32 KiloVAr N/A

Pagina 253 - CHARACTERISTIC CURVES

B-50 DGC-2020 Modbus Communication 9400200990 Rev K Register Description Type Units Scaling Factor R/W Range 46018 J1939-Rated RPM Uint32 Raw ECU P

Pagina 254

9400200990 Rev K DGC-2020 Modbus Communication B-51 Register Description Type Units Scaling Factor R/W Range 46052 J1939-ADEC Cylinder Cutout Code

Pagina 255

B-52 DGC-2020 Modbus Communication 9400200990 Rev K Register Description Type Units Scaling Factor R/W Range 46104 J1939-ADEC T Intercooler Limit Hi

Pagina 256

9400200990 Rev K DGC-2020 Tuning PID Settings i APPENDIX C  TUNING PID SETTINGS TABLE OF CONTENTS APPENDIX C  TUNING PID SETTINGS ...

Pagina 257

P0053-51SETTINGSGENERAL SETTINGSCOMMUNICATIONSSYSTEM PARAMSPROGRAMMABLE INPUTSPROGRAMMABLE OUTPUTSALARM CONFIGURATIONGENERATOR PROTECTIONBREAKER MANAG

Pagina 258

ii DGC-2020 Tuning PID Settings 9400200990 Rev K This page intentionally left blank.

Pagina 259

9400200990 Rev K DGC-2020 Tuning PID Settings C-1 APPENDIX C  TUNING PID SETTINGS INTRODUCTION The LSM-2020 (Load Share Module) and DGC-2020 utiliz

Pagina 260

C-2 DGC-2020 Tuning PID Settings 9400200990 Rev K TUNING PROCEDURES Voltage Controller Tuning Procedure The voltage controller is tuned prior to the

Pagina 261

9400200990 Rev K DGC-2020 Tuning PID Settings C-3 Var/PF Controller Tuning Procedure Once desired voltage controller performance is obtained, the Va

Pagina 262

C-4 DGC-2020 Tuning PID Settings 9400200990 Rev K and the speed it is trying to reach. The important thing is that the generator’s output behaves in

Pagina 263

9400200990 Rev K DGC-2020 Tuning PID Settings C-5 KD - Derivative Gain If the performance with KP and KI alone is satisfactory, you may stop here. O

Pagina 264

C-6 DGC-2020 Tuning PID Settings 9400200990 Rev K This page intentionally left blank.

Pagina 266

ROUTE 143, BOX 269 HIGHLAND, IL 62249 USA http://www.basler.com, [email protected] PHONE +1 618-654-2

Pagina 267

2-8 DGC-2020 Human-Machine Interface 9400200990 Rev K o UTC OFFSET o DST ENABLED  VIEW DATE/TIME  VERSION INFO o FIRMWARE VERSION o BOOT CODE VE

Pagina 268

9400200990 Rev K DGC-2020 Human-Machine Interface 2-9 o RATED FREQ o RATED RPM o COOLDWN TIME o OFF MODE COOLDN o EPS  EPS THRESHLD  LOW LINE OV

Pagina 269

2-10 DGC-2020 Human-Machine Interface 9400200990 Rev K o AEM SETUP  ENABLE  CANBUS ADDR (Visible when AEM-2020 is enabled.)  VERSION INFO (Visi

Pagina 270

9400200990 Rev K DGC-2020 Human-Machine Interface 2-11 PROGRAMMABLE INPUTS  CONFIGURABLE INPUTS o INPUT X (X = 1 to 26)  ALARM CONFIG  ACTIVATN

Pagina 271

2-12 DGC-2020 Human-Machine Interface 9400200990 Rev K  OVER 2  THRESHOLD  ALARM CONFIG  UNDER 1  THRESHOLD  ALARM CONFIG  UNDER 2  THRESHOL

Pagina 272

9400200990 Rev K DGC-2020 Human-Machine Interface 2-13 o MAINTENANCE INTERVAL  ENABLE  THRESHOLD o BATTERY OVERVOLTAGE  ENABLE  THRESHOLD o LOW

Pagina 273

First Printing: November 2006 Printed in USA © 2009 Basler Electric, Highland Illinois 62249 USA All Rights Reserved January 2009 CONFIDENTIAL

Pagina 274

NOTE The HIGH COOLANT TEMP and LOW OIL PRESSURE alarms have an ARMING DLY setting that disables the alarm for the specified time after engine startup.

Pagina 275

9400200990 Rev K DGC-2020 Human-Machine Interface 2-15  CURVE  ALARM CONFIG  32 REVERSE POWER o 3 / 1 PHASE SETTINGS  PICKUP  HYSTERESIS  TI

Pagina 276

2-16 DGC-2020 Human-Machine Interface 9400200990 Rev K o REGUL OFFSET o CLOSING ANGLE o VG>VB o TIME DELAY o FAIL DELAY BIAS CONTROL  AVR BIAS

Pagina 277

9400200990 Rev K DGC-2020 Human-Machine Interface 2-17  BL ALG MAX (Visible when LSM-2020 is enabled.)  BL ALG MIN (Visible when LSM-2020 is ena

Pagina 278

REAR PANEL All DGC-2020 terminals and connectors are located on the rear panel. Rear panel terminals and connectors are illustrated in Figure 2-4. (To

Pagina 279

9400200990 Rev K DGC-2020 Human-Machine Interface 2-19 Table 2-2. Rear Panel HMI Descriptions Locator Description A, D The majority of external, DG

Pagina 280

2-20 DGC-2020 Human-Machine Interface 9400200990 Rev K This page intentionally left blank.

Pagina 281 - DATA FORMATS

9400200990 Rev K DGC-2020 Functional Description i SECTION 3  FUNCTIONAL DESCRIPTION TABLE OF CONTENTS SECTION 3  FUNCTIONAL DESCRIPTION ...

Pagina 282

ii DGC-2020 Functional Description 9400200990 Rev K AUTO Mode (Running)...

Pagina 283

SECTION 3  FUNCTIONAL DESCRIPTION INTRODUCTION This section describes how the DGC-2020 functions. A detailed description of each function block is pr

Pagina 284

9400200990 Rev K DGC-2020 Introduction iii REVISION HISTORY The following information provides a historical summary of the changes made to this ins

Pagina 285

3-2 DGC-2020 Functional Description 9400200990 Rev K Zero Crossing Detection The zero crossing of A-phase to B-phase or A-phase to C-phase (user-sel

Pagina 286

9400200990 Rev K DGC-2020 Functional Description 3-3 Coolant temperature sender connections are made at terminals 10 and 11 (sender common). Fuel Le

Pagina 287

3-4 DGC-2020 Functional Description 9400200990 Rev K Connections for the programmable inputs are provided at terminals 15 (Input 16) through 30 (Inp

Pagina 288

9400200990 Rev K DGC-2020 Functional Description 3-5 USB The rear-panel, mini-B USB socket enables local communication with a PC running BESTCOMSPlu

Pagina 289

ECU Parameter Metric Units English Units Update Rate Decimal Place  SPN Total fuel used liters gallons requested 1.5 s none 250 Trip fuel liters

Pagina 290

9400200990 Rev K DGC-2020 Functional Description 3-7 Table 3-3. Diagnostic Information Obtained Over the CANbus Interface Parameter Transmission Rep

Pagina 291

3-8 DGC-2020 Functional Description 9400200990 Rev K 265, SD BANK 2 TEST 266, SD SPD DEMAND AN 267, SD SPDMTEST BNCH 269, SD LOAD PLS ANLG 270, SD

Pagina 292

9400200990 Rev K DGC-2020 Functional Description 3-9 input is open (emergency stop condition), the Pre-Start, Crank, and Fuel outputs open. When the

Pagina 293

3-10 DGC-2020 Functional Description 9400200990 Rev K Generator Exerciser The unit will start at the designated time and will run for the specified

Pagina 294

9400200990 Rev K DGC-2020 Functional Description 3-11 The type of response given for a local request depends on the operating mode of the DGC-2020.

Pagina 295

iv DGC-2020 Introduction 9400200990 Rev K BESTCOMSPlus Version and Date Change 2.03.00, 01/09  Added Export to File feature.  Added settings for

Pagina 296

3-12 DGC-2020 Functional Description 9400200990 Rev K Breaker close sources are:  The DGC-2020 itself when the automatic transfer (ATS) feature is

Pagina 297

9400200990 Rev K DGC-2020 Functional Description 3-13 Table 3-4. Event List Event String Event Description Event Type 27-1 UNDVOLT TRP A 27-1 Unde

Pagina 298

3-14 DGC-2020 Functional Description 9400200990 Rev K Event String Event Description Event Type ATS INPUT CLOSED ATS Input Status AUTO RESTART A

Pagina 299 - Bias Control Settings

9400200990 Rev K DGC-2020 Functional Description 3-15 Event String Event Description Event Type GN BKR OP FL P Generator Breaker Fail to Open Pre

Pagina 300 - Bus Condition Detection

3-16 DGC-2020 Functional Description 9400200990 Rev K Event String Event Description Event Type LOST ECU COMM P Loss of ECU Communication Pre-Ala

Pagina 301 - Senders

9400200990 Rev K DGC-2020 Functional Description 3-17 Event String Event Description Event Type RTD_IN_X_O2 A (X = 1 to 8) User Configurable Analo

Pagina 302

3-18 DGC-2020 Functional Description 9400200990 Rev K This page intentionally left blank.

Pagina 303

9400200990 Rev K DGC-2020 BESTCOMSPlus Software i SECTION 4  BESTCOMSPlus SOFTWARE TABLE OF CONTENTS TTSECTION 4  BESTCOMSPlus SOFTWARE...

Pagina 304 - Control

ii DGC-2020 BESTCOMSPlus Software 9400200990 Rev K Frequency Protection (81O/U) ...

Pagina 305 - Protection

9400200990 Rev K DGC-2020 BESTCOMSPlus Software iii Figure 4-17. ECU Setup ...

Pagina 306

9400200990 Rev K DGC-2020 Introduction v Firmware Package Version and Date Change 1.08.01, 01/09  Changed time dial range of 51 element fixed time

Pagina 307

iv DGC-2020 BESTCOMSPlus Software 9400200990 Rev K Figure 4-78. Metering, Inputs, Remote Thermocouple Inputs...

Pagina 308

SECTION 4  BESTCOMSPlus SOFTWARE INTRODUCTION BESTCOMSPlus is a Windows®-based, PC application that provides a user-friendly, graphical user interfac

Pagina 309

Table 4-1. System Requirements for BESTCOMSPlus and the .NET Framework Component Requirement Processor 400 MHz RAM 128 MB 25 MB (if .NET Framework is

Pagina 310

The BESTCOMSPlus splash screen is shown for a brief time. See Figure 4-3. Figure 4-3. Splash Screen The BESTCOMSPlus platform window opens. If a DG

Pagina 311

Click on the Activate button when you are ready to enter the activation key you received from Basler Electric. The Device Needs Activated pop-up will

Pagina 312 - Metering

Figure 4-7. DGC-2020 Connection USB Communication If connecting to the DGC-2020 through a USB cable, select USB via Serial RS232, USB, and enter COM

Pagina 313

Modem Communication If connecting to the DGC-2020 through a telephone line, select USB via Serial RS232, Modem, and enter Phone Number. To select the

Pagina 314

10.0.0.0 - 10.255.255.255 172.16.0.0 - 172.31.255.255 192.168.0.0 - 192.168.255.255 If the LSM-2020 is operating on an isolated network, the Sub

Pagina 315

Figure 4-10. Processing, Please Wait… MENU BARS The menu bars are located near the top of the BESTCOMSPlus screen (see Figure 4-1). The upper menu ba

Pagina 316

Help  About... View general, detailed build, and system information Lower Menu Bar (DGC-202

Pagina 317

vi DGC-2020 Introduction 9400200990 Rev K DGC-2020 Hardware Version and Date Change P, 01/09  Release firmware package 1.08.01 and BESTCOMSPlus 2.0

Pagina 318

GENERAL SETTINGS General DGC-2020 settings consist of settings controlling the HMI display and indicators. Additional general settings include style n

Pagina 319

Style Number When a PC operating BESTCOMSPlus is communicating with a DGC-2020, the style number of the DGC-2020 is automatically displayed on the BES

Pagina 320

When on-line, read-only information includes the application versionY, boot code versionZ, application buildAA, serial numberBB, application part numb

Pagina 321

9400200990 Rev K DGC-2020 BESTCOMSPlus Software 4-13

Pagina 322

 OEM Access. This password level allows access to all settings. The default, OEM-access password is OEM.  Settings Access. This password level all

Pagina 323

Figure 4-15. Clock Setup A UTC Offset (min): Adjustable from -1,440 to 1,440 minutes in increme

Pagina 324

selected, the Fuel Solenoid output will still close during cranking and genset operation to provide a separate indication that the genset is running.

Pagina 325

9400200990 Rev K DGC-2020 BESTCOMSPlus Software 4-17 secondary base speed is 1,800 rpm. The Accelerator Position settingC is expressed as a percenta

Pagina 326

Figure 4-17. ECU Setup A ECU Type: Standard, Volvo Penta, MTU MDEC, MTU ADEC, or MTU ECU7. B Sp

Pagina 327

9400200990 Rev K DGC-2020 BESTCOMSPlus Software 4-19  81O Trip Alarm  81U Trip Alarm  27-1 Trip Pre-Alarm  27-2 Trip Pre-Alarm  32 Trip Pr

Pagina 328

9400200990 Rev K DGC-2020 Introduction vii CONTENTS SECTION 1  GENERAL INFORMATION ...

Pagina 329

 Overspeed Alarm  Scheduled Maintenance Pre-Alarm  Switch Not in Auto  Transfer Fail Alarm  Virtual Output X Status (X = 1 to 8)  Weak Bat

Pagina 330

Figure 4-19. RS-485 Setup A Baud Rate: A value of 1200, 2400, 4800, or 9600 may be selected. B

Pagina 331

4-22 DGC-2020 BESTCOMSPlus Software 9400200990 Rev K immediately. Furthermore, if an Off Mode Cooldown is in progress and the OFF button is pressed,

Pagina 332 - TUNING PROCEDURES

9400200990 Rev K DGC-2020 BESTCOMSPlus Software 4-23 Single-Phase Override The DGC-2020 will switch to single-phase voltage sensingQ when a contact

Pagina 333

Figure 4-20. System Settings A Generator Connection: Delta, Wye, 1-Phase A-B, 1-Phase A-C, or

Pagina 334

Contact Expansion Module A J1939 AddressC must be entered when the optional CEM-2020 is enabledD. Select number of CEM-2020 outputsE. Analog Expansion

Pagina 335

Figure 4-22. Engine Crank Settings A Cranking Style: Cycle or Continuous. B Number of Crank Cy

Pagina 336

Exercise Timer The exercise timer is used to start the genset at a predetermined time and run for the user-defined period. The modeA defines how often

Pagina 337

Bus Transformer Settings Primary and secondary bus transformer ratings are used by the automatic transfer switch function, which monitors a single-pha

Pagina 338

Figure 4-26. Contact Inputs Settings A Alarm Configuration: None, Alarm, or Pre-Alarm. B Activ